台达 MS300 是精巧矢量型变频器,常用于风机、水泵、传送带等轻载场景,故障代码清晰、参数易调试,但现场常遇到上电、过流、过压、端子控制、参数异常等问题。以下是OCA加速过流代码 + 成因 + 一步到位解决方案。
OCA :加速过流
成因:
加速时间太短、电机短路 / 绝缘差、负载过重、变频器偏小
解决:
1.延长 01-07 加速时间(默认 10.0s → 15–30s)
2.降低载波频率(01-04)、减小转矩提升(01-12)
3.断开电机线空载试机:不跳 → 电机 / 线路问题;仍跳 → 变频器 IGBT 损坏