台达 MS300 是精巧矢量型变频器
常用于风机、水泵、传送带等轻载场景,故障代码清晰、参数易调试,但现场常遇到上电、过流、过压、端子控制、参数异常等问题。
以下是过压故障代码 + 成因 + 一步到位解决方案。
OVA:加速过压
OVD:减速过压(最常见)
OVN:恒速过压
成因:
输入电压过高、减速太快、无制动电阻、大惯性负载
解决:
1.确认输入 380V±15%
2.延长减速时间(01-08)
3.加装制动电阻、开启过压失速(07-01=1)
台达 MS300 是精巧矢量型变频器选型型号
1. 单相 230V (1P 230V) — 功率:0.2~2.2kW
VFD1A6MS21ANSAA (0.2kW, 1.6A)
VFD2A8MS21ANSAA (0.4kW, 2.8A)
VFD4A8MS21ANSAA (0.75kW, 4.8A)
VFD7A5MS21ANSAA (1.5kW, 7.5A)
VFD11AMS21ANSAA (2.2kW, 11A)
2. 三相 230V (3P 230V) — 功率:0.2~15kW
VFD1A6MS23ANSAA (0.2kW, 1.6A)
VFD2A8MS23ANSAA (0.4kW, 2.8A)
VFD4A8MS23ANSAA (0.75kW, 4.8A)
VFD7A5MS23ANSAA (1.5kW, 7.5A)
VFD11AMS23ANSAA (2.2kW, 11A)
VFD17AMS23ANSAA (3.7kW, 17A)
VFD25AMS23ANSAA (5.5kW, 25A)
VFD33AMS23ANSAA (7.5kW, 33A)
VFD49AMS23ANSAA (11kW, 49A)
VFD59AMS23ANSAA (15kW, 59A)
3. 三相 460V (3P 460V) — 功率:0.4~22kW
VFD2A8MS43ANSAA (0.4kW, 2.8A)
VFD4A2MS43ANSAA (0.75kW, 4.2A)
VFD5A5MS43ANSAA (1.5kW, 5.5A)
VFD9A0MS43ANSAA (2.2kW, 9A)
VFD13AMS43ANSAA (3.7kW, 13A)
VFD17AMS43ANSAA (5.5kW, 17A)
VFD24AMS43ANSAA (7.5kW, 24A)
VFD32AMS43ANSAA (11kW, 32A)
VFD38AMS43ANSAA (15kW, 38A)
VFD45AMS43ANSAA (18.5kW, 45A)
VFD59AMS43ANSAA (22kW, 59A)
工易自营